EGP Natural Gas Specification

Item

Specification

Test Method

Minimum Temperature

2°C

 

Maximum Temperature

50°C

 

Wobbe Index

Minimum 46.0
Maximum 52.0

ISO 6976;
or ASTM D3588

Oxygen

Maximum 0.2% by volume

ISO 6974 and ISO 6975;
or ASTM D1945

Total Inerts

Maximum 7% by volume

ISO 6974 and ISO 6975;
or ASTM D19455

Hydrocarbon Dew Point

Maximum 2°C
At 3,500 kPag gauge

 

Water Content

Minimum water dew point of 0°C at MAOP. This is equivalent to a maximum water content of 75 mg/m3 at 14,895 kPa and 70 mg/m33 at 16,550 kPa. Note: the m3 is at standard conditions

ASTM D1142

Hydrogen Sulphide

Maximum 5.7 mg/m3

ISO 6326

Total Sulphur (including odourant)

Maximum 50 mg/m3

ASTM D1072

Total Sulphur (excluding odourant)

Maximum 40 mg/m3

ASTM D1072

Notes:

  1. All values measured or specified at 15C and 101.325 kPa gauge unless otherwise stated.
  2. Wobbe Index means the Higher Heating Value divided by the square root of the relative density of the gas, both measured at the same time.
  3. For the purposes of this EGP Natural Gas Specification, carbon dioxide and nitrogen will be deemed to be inert gases.